Class I & II, Division 1, Group C-G, FM Approved Purge Control System (“X-Purge”) for use on Customer-Supplied Enclosure.
Features:
- Factory Mutual Approved for Class I and Class II, Division 1, Group C-G Hazardous Areas
- Comes Completely Assembled with All Required Parts - Solenoids, Air-in Gauge, Regulator, Outlet Valve, and Spark Arrestor
- Power and Signal Interlocks Included Standard - Alarm Contacts and up to 31 Signals
- Environmentally and Financially Friendly - Only Uses Compressed Air when Internal Pressure Drops below Preset Level
- Automatic Self-Adjusting Microprocessor Controlled Purge System with Self Diagnostics
- May Be Mounted Flush or Mounted without Use of Enclosure's Internal Space Using Included Interface Box
Options:
- Air Connection Kit
- Pac-Seal Kit
Specifications
| MATERIAL |
|
|
Purge Control main panel,
Interface Box,
all mounting screws |
304 Stainless Steel |
| I/O Casting and lid |
Cast Aluminum |
| I/O Casting bolts |
Irodited Steel |
| PHYSICAL |
|
| Purge Controller |
17.5 Height (H)
11.5” Width (W)
10.81” Depth (D)
4.0” D-Inside
5.63” D-Outside
25 lbs. |
| Interface Box |
17.5” Height (H)
11.5” Width (W)
5.0” Depth (D)
5 lbs |
| ENVIRONMENTAL |
|
| Operating Temperature |
32-122°F |
| Storage Temperature |
32-158°F |
| Relative Humidity |
10-95% Non-condensing |
| ELECTRICAL |
|
| Power Usage |
5 watts maximum |
| Switching Capacity |
120V/10A or 240V/5A maximum |
| FCC Class A computing device |
|
| PRESSURE AND AIR REQUIREMENTS |
|
|
Incoming Air Pressure
(Customer Air Input) |
20-60 psi |
| Operating Pressure |
1” - 4” of water column |
| Air Flow During Purge |
40-300 SCFH |
| CONTROLS MONITORING |
|
| Microprocessor based |
|
|
|
 |
 |
 |
 |
|
 |

| Accessories for this product... |
|
|
|

|