  9017 Class I&II Division 2 Z-Purge Control System
  Division 2 purge control


 
Please call for pricing


Product Code: DDD-9017
Qty:

Description Technical Specifications
 
The "Z" Purge Control System is FM Approved Class I & II, Division 2 Group B-G. Completely  Pre-Assembled for Easy Installation with Short Purge Time (Less Than 2 Minutes per Cubic Foot) and Low Internal Pressure, this Purge Control System includes a Built-In Vent Valve with Spark Arrestor, a Built-In Flow Meter and Pressure Gauge for Easy Set-Up and Operation.
 
The concept of preventing the ignition of flammable elements in a hazardous area using a purge system per NFPA 496 is actually very simple, though its implementation is somewhat more complex. The basic idea in purging electronic equipment is to keep electronics that have the potential of producing sparks or high temperatures separate from the explosive elements. This is accomplished by placing the electronics in an enclosure that is sealed against the entry of the outside atmosphere.
 
To ensure that none of the external atmosphere is within the enclosure, the purge system starts by replacing the internal atmosphere with four volumes of inert gas, supplied via a compressed air or compressed nitrogen line. Only after this purge has occurred are electrical supplies and signals connected to the inside of the enclosure. Because no enclosure can be perfectly sealed, after the purge is complete the purge system must ensure that no exchange of gases can occur. This is accomplished by maintaining a slight positive pressure within the enclosure. If this positive pressure falls below a preset level, the electrical supplies and signals are disconnected from the inside of the enclosure.
 
In Division 2 areas, where explosive elements are only present under abnormal conditions, the connecting and disconnecting of the electrical supply and signals is controlled by the operator. The purge system must provide an indication to the operator in the event of the loss of pressurization. This can be accomplished via an included indicator or a system connected to alarm contacts. The purge process itself is also manual.
 
In Division 1 areas, where explosive elements can reasonably be expected to be present under normal conditions, the entire process must be automatically controlled by the purge system. The purge system controls the purge and automatically disconnects the electrical supply and signals upon loss of internal pressure. Alarm contacts are also provided to alert the user.

Accessories for this product...
Over Pressure Relief Valve (4” Water Column)

Add
Pressure Alarm Switch with 2 "Form C" Contact & LED

Add
Over Pressure Relief Valve (½ PSI)

Add
9026 Pac Seal Connection Kit

Add
9047 Air Connection Kit

Add


Browse for more products in the same category as this item:

Intrinsically Safe > Computer Accessories
Daisy Data
Intrinsically Safe


TPI-460 Dual Channel, 20Mhz Oscilloscope with True RMS DMM $995.95
Signal Extender System
CDI-C-CLAMP Steel Balancing C-Clamp Replacement Correction Weights
Cardan Bracket Kit $4,200.00
Extech MO210 Pocket Moisture Meter $99.99
Spinning laser D23 $10,300.00
Monarch Instrument Smart-Laser Speed Sensor $1,275.00
UP-2000S Analog Ultrasonic Detection System $3,695.00
Wilcoxon 731A Ultra Low Vibration Sensor and Power Unit $1,395.00
Reliability Direct, Inc.
1010 East Main Street
League City, TX 77573
 Contact Us
 Become an Affiliate
 Privacy Policy
 Send Us Feedback